2000531
8603
Varen er på lager.
Varen er bestilt fra leverandør og leveringsdato er bekreftet.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varen må bestilles fra leverandør.
Varen befinner seg på fjernlager.
Varen er bestilt fra leverandør, men leveringsdato er ikke bekreftet.
Varene bestilles fra vår leverandørs lager.
Ubekreftet - Ta kontakt med kundesenter for nærmere informasjon.
Totalt antall treff:
|
Antall artikler funnet:
|
Handlevogn
Handlevognen er tom.
Ex XenonStrobe STExB2 X15 24vDC RED
SS316L IP66 15J Ex-db-IIC-Gb-T4
Varenr:
STEXB2X15024AS2R.1
|
|
STExB2X15 Xenon Strobe Beacon 15 Joule
in 316L Stainless Steel enclosure
The STExB2X15 is an explosion proof 15 Joule Xenon beacon. The robust IP66 corrosion proof 316L stainless steel enclosure ensures the STExB2X15 is suitable for all Zone 1, 2, 21 & 22 hazardous location signalling applications.
The STExB2X15 beacons produce a high output Xenon flash required for effective signalling in environments with elevated levels of ambient light. The field replaceable colour filter enhances the strobe and is constructed from UV stable PC. The stainless steel enclosure features a threaded flame path, four cable entries and a large termination area - all of which significantly reduce installation time.
Features:
• Robust corrosion proof 316L stainless steel enclosure
• Ingress protection IP66
• Automatic synchronisation on multi-beacon systems
• Choice of three flash rates: 1Hz, 1.5Hz and double flash
• User replaceable Xenon tube mechanically secured against shock & vibration
• 316 Stainless Steel guard included as standard
• Field replaceable UV stable lens colour filter
• 316 Stainless steel stopping plugs included
• 4 x M20 cable entries
• Stainless steel fasteners
• Duplicate cable terminations (in & out for daisy-chain installations)
Approvals:
IECEx ULD 16.0017X
IEC 60079-0 : 2011
IEC 60079-1 : 2014
IEC 60079-31 : 2013
ATEX DEMKO 16 ATEX 1466X
EN 60079-0 : 2012 + A11 : 2013
EN 60079-1 : 2014
EN 60079-31 : 2014
TR-CU Ex EAC certificate: RU C-GB.AA71.B.00109
Coding:
• Ex db IIC T4 Gb Ta. -50° to +70°C
• Ex tb IIIC T130°C Db Ta. -50° to +70°C
Specification:
Energy: | 15 Joules (10Ws) |
Flash rate: | 1Hz (60 fpm), 1.5Hz (90fpm) & double flash |
Peak Candela: | 1,500,000 cd - calculated from energy (J) |
Eff. Intensity cd: | 750 cd - calculated from energy (J) |
Peak Candela: | 114,854 cd - measured ref to I.E.S |
Eff. Intensity cd: | 666.92 cd - measured ref to I.E.S |
Lens colours: | Red, Amber, Yellow, Green, Blue, Clear & Magenta |
Voltages DC: | 24vDC; 48vDC |
Voltages AC: | 115vAC; 230vAC |
Ingress protection: | EN60529: IP66 |
Enclosure matl: | 316L Stainless Steel |
Enclosure finish: | Chromated & powder coated |
Colour: | RAL3000 Red |
Cable entries: | 4 x M20 ISO (3 x stopping plugs included as standard) |
| Adaptors to M25, 1/2" & 3/4" NPT can be specified |
Terminals: | 0.5 - 2.5mm² (20-14 AWG) |
Enclosure volume: | <2 litres |
Line monitoring: | Blocking diode included |
| EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor |
| or diode (DC versions) can be fitted |
Grounding stud: | M5 |
Tube life: | Emissions are reduced to 70% after 8 million flashes |
Temp. range: | -50° to +70°C (-58°F to +158°F) |
Relative humidity: | 90% at 20°C [68°F] |
Weight: | 6.0kg / 13.23lbs |
*All candela data is representative of performance with clear lens at optimum voltage.
Part Codes: STExB2 X15 [u] [e] [m] [s] [x] . [y]
Version: | Part code: | |
| | |
Product type: | STExB2 | Explosion proof Beacon |
Type: | X15 | 15J Xenon Beacon |
| | |
Voltage: [u] | 024 | 24vDC |
| 048 | 48vDC |
| 115 | 115vAC |
| 230 | 230vAC |
| | |
Cable Entry Type: [e] | A | 4 x M20x1.5mm (Default) |
| B | 2 x 1/2" NPT - adaptors |
| C | 2 x 3/4" NPT - adaptors |
| D | 2 x M25x1.5mm - adaptors |
| E | 1 x 1/2" NPT - adaptor |
| F | 1 x 3/4" NPT - adaptor |
| G | 1 x M25x1.5mm - adaptor |
| H | 3 x 1/2" NPT - adaptors |
| I | 3 x 3/4" NPT - adaptors |
| J | 3 x M25x1.5mm - adaptors |
| Note: | M20 stopping plugs for unused |
| | entries supplied with all options |
| | |
Adaptor/Stopping | B | Brass |
plug material: [m] | N | Nickel Plated |
| S | Stainless Steel (Default) |
| | |
Guard material: [s] | 1 | A2 304 Stainless Steel |
| 2 | A4 316 Stainless Steel (Default) |
| | |
Product version: [v] | A1 | IECEx & ATEX Group II 2G/D |
| | Zone 1, 2, 21 & 22 (Default) |
| | (A1 is not included in the Part Code |
| | because of space limitations, and |
| | as this is the only option) |
| | |
Enclosure colour: [x] | R | Red (Default) |
| | |
Lens colour: .[y] | .1 | R Red |
| .2 | A Amber (Orange) |
| .3 | Y Yellow |
| .4 | G Green |
| .5 | B Blue |
| .7 | C Clear (Transparent) |
| .8 | M Magenta |
Example part code: | STExB2 X15 [u] [e] [m] [s] [x] . [y] |
| STExB2 X15 024 A S 2 R . 1 |
| |
Explanation of tehe above: | |
Product type: | "STExB2" = Explosion proof Beacon |
Type: | "X15" = 15J Xenon Beacon |
Voltage: [u] | "024" = 24vDC |
Cable Entry: [e] | "A" = 4 x M20x1.5mm |
Stopping plug: [m] | "S" = Stainless Steel (Standard) |
Bracket material: [s] | "2" = A4 316 Stainless Steel Guard |
Enclosure colour: [x] | "R" = Red Enclosure colour |
Lens colour: .[y] | ."1" = (R) Red Lens colour |
Effective Candela lens colour factor:
Red | Amber | Yellow | Green | Blue | Clear |
0.15 | 0.51 | 0.86 | 0.49 | 0.12 | 1.00 |
Current Consumption:
Version: | | Voltage: | Current: |
24vDC | | 20-28vDC | 822mA |
48vDC | | 42-54vDC | 342mA |
115vAC | 50/60Hz | 110-125vAC | 328mA |
230vAC | 50/60Hz | 220-240vAC | 168mA |